Specifications for Three Phase to Single Phase UPS
| Model |
ARS 310 |
| Rating |
10KVA to 50KVA |
| AC INPUT |
415V + 15% -15%, Three Phase Input |
| Frequency |
50Hz ± 6% |
| DC VOLTAGE: |
360 / 392VDC |
| Charging Time |
12 Hours for 90% of full Capacity |
| Charger Type |
CVCC (Constant Current Constant Voltage type) |
| INVERTER: |
|
| Technology |
DSP based, IGBT Switching |
| Output Voltage |
230V AC single Phase |
| Frequency |
50Hz ± 0.1Hz |
| Waveform |
PWM Sine wave |
| Harmonic Distortion |
Less than 3% on Linear Load |
| Inverter Efficiency |
Upto 90% below 20KVA and upto 93% for 30 to 50KVA |
| Power Factor |
0.8 |
| Overload |
110 % for 5 min, 150% for 30 sec |
| Crest Factor |
3 : 1 |
| Audible Noise |
Less than 65 dB at 1 Meter |
| DISPLAY : |
|
| Digital LCD Display for |
R,Y,B Input and Output Voltages, Output currents & Frequency, DC Voltage , Battery and Load Percentage and All Faults |
| GENERAL: |
|
| Operating temperature |
0°C to 40°C |
| Humidity |
Max 95%, Non-condensing |
| PROTECTIONS : |
Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage, Mains Under & Overvoltage, Mains Single Phasing. |
| INDICATIONS & ALARMS: |
|
| a) Mains on |
LED Indication |
| b) Inverter |
LED Indication |
| c) Batt Low |
LED Indication & Alarm |
| d) Fault |
LED Indication & Alarm |
| e) Overload |
LED Indication & Alarm |
| BYPASS |
Static Switch (optional) |